SpecSeal® SSP Firestop Putty excels at sealing cabling penetrations and outlet boxes. SSP Putty is non-hardening and easily hand works around grouped cabling penetrations forming a re-enterable seal allowing for future work. When applied with outlet boxes, SSP Putty easily works into voids and seams forming a continuous seal against fire and the products of combustion.
Putty Pads Physical Properties | |
---|---|
Color: | Red |
Odor: | None |
Density: | 1.45 kg/L (12.08 lb/gal) |
Solids: | 100% |
In-Service Temperature: | -10°F to 120°F (-23°C to 49˚C) |
Installation Temperature: | Less than 100°F (38°C) |
Storage Temperature: | Less than 100°F (38°C) |
STC Rating: | 62 (Relates to specific construction) (ASTM E 90-04/ASTM C919) |
VOC Content**: | 0.00 lbs/gal (0.0g/L) |
Shelf Life: | No Limit |
**ASTM D 3960 and EPA Federal Reference Method 24. |
Putty Physical Properties | |
---|---|
Color: | Red |
Odor: | None |
Density: | 1.45 kg/L (12.08 lb/gal) |
Solids: | 100% |
Expansion Begins: | 230°F (110˚C) |
Volume Expansion: | > 500% (free expansion) |
In-Service Temperature: | -10°F to 120°F (-23°C to 49˚C) |
Storage Temperature: | Less than 100°F (38°C) |
STC Rating: | 62 (Relates to specific construction) (ASTM E 90-04/ASTM C919) |
VOC Content**: | 0.00 lbs/gal (0.0g/L) |
Shelf Life: | No Limit |
**ASTM D 3960 and EPA Federal Reference Method 24. |
Item # | Case Qty. (min) | Qty. | UPC # 730573 | Description | Weight |
---|---|---|---|---|---|
SSP100 | 6 | 1 | 02100 | 36 in3 (0.6 liter) bar | 2.3 lbs (1.04 kg) |
SSP28 | 1 | 1 | 02101 | 24 in3 (0.4 liter) bar | 1.85 lbs (0.84 kg) |
SSP4S | 20 | 1 | 02200 | 7.25” x 7.25” x 3/16” (18.4 x 18.4 x .5 cm) pad | 0.59 lbs (.27 kg) |
SSP9S | 20 | 1 | 02300 | 9.00” x 9.00” x 3/16” (22.9 x 22.9 x .5 cm) pad | 0.99 lbs (.44 kg) |
Underwriters Laboratories Inc.
Visit Website →
Factory Mutual Research (FM)
Visit Website →
International Firestop Council (IFC)
Visit Website →
Fire Safe North America
Visit Website →
Firestop Contractors International Association (FCIA)
Visit Website →
International Codes Council (ICC)
Visit Website →
National Fire Protection Association (NFPA)
Visit Website →
The Construction Specifications Institute
Visit Website →
The American Institute of Architects
Visit Website →
Association of the Wall and Ceiling Industries International (AWCI)
Visit Website →
BICSI
Visit Website →
The perfect brochure to use as a reference tool for any STI Product on the market.
Our complete product brochure designed for international markets.
Our complete EZ-Path® product line in one convenient location.
Our complete brochure for the EZ-Path® Retrofit Device.
EZ-Path® saves time, money, and resources by removing ongoing downstream costs.
STI is dedicated to providing our clients and partners with the industry’s most advanced cost-effective solutions for perimeter fire barrier systems.
The terms firestop and fireblock are very similar sounding, but there are critical differences between these two practices. Here are the major differences.
E-Wrap™ Endothermic Wrap is the ideal solution for fire protection of critical circuits and infrastructure such as fire pumps, signaling equipment, elevators, alarms, process control equipment, or Emergency Responder Communications Enhancement Systems (ERCES).
We understand the nuances of firestopping head-of-wall joints and other joint systems installed into or between wall systems. We offer flexible joint sealants and sprays or gasket materials that allow for dynamic movement.
+ User Guide: US & Canada
+ User Guide: Europe & Middle East
+ Electrical & DataCom User Guide
+ EZ-Path® Fire Rated Pathway
STI warrants that its products will be free of defects for one year from the date of purchase. In the event a product does not conform to this warranty, the sole and exclusive remedy is, at STI’s option, replacement of the product or refund of the purchase price. The warranty provided herein shall be void and of no effect in the event that the product is not installed in accordance with STI’s published instructions, listed systems and applicable building and safety codes. THIS WARRANTY IS IN LIEU OF ALL OTHER REPRESENTATIONS AND EXPRESSED OR IMPLIED WARRANTIES (including the implied warranties of merchantability or fitness for a particular use) AND UNDER NO CIRCUMSTANCES SHALL STI BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, INCLUDING, WITHOUT LIMITATION, ANY LOSS OF REVENUE, PROFIT OR USE. Prior to use, the user shall determine the suitability of the product for its intended use, and the user assumes all risks and liability for subsequent use. No person other than an officer of STI is authorized to bind STI to any other warranty for any product for which this warranty is issued.
Construction Joints
View PDF | View DWG
Curtain Wall
View PDF | View DWG
Did you know that many specifications for firestopping reference older fire test standards or obsolete products?
Let our firestop experts assist by reviewing your firestop specifications and making appropriate recommendations. STI provides this service free of charge.