The primary difference between Canadian test requirements and those found in the US relates to vented combustible penetrants such as plastic pipes intended for use in drain, waste, or vent (DWV) applications. Said penetrating items must be tested with a minimum positive furnace pressure differential of 50 Pa compared to 2.5 Pa for the US. Other than vented combustible penetrants, all other penetrating items are tested to 2.5 Pa.
| STI 50 Pa Testing for
Combustible Pipes |
System No. |
Pipe Diameter (mm) |
STI Product |
PDF |
DWG |
DOC |
| SPC87 |
Max 150 mm FRPP pipe. Collar. 2 Hr. |
SSWRED, SSWBLU, or Factory Collar |
 |
|
|
| SPC88 |
Max 100 mm ABS or FRPP pipe. Collar. 2 Hr. |
SSWRED, SSWBLU, or Factory Collar |
 |
|
|
| SPC89 |
Max 50 mm ABS or FRPP pipe. Tuck-in. 2 Hr. |
SSWBLU |
 |
|
|
| SPC90 |
Max 100 mm PVDF pipe. Collar. 2 Hr. |
SSWRED, SSWBLU, or Factory Collar |
 |
|
|
| |
| STI ULC Testing (Supplemental
to UL/cUL Listings) |
System No. |
Description |
STI Product |
PDF |
DWG |
DOC |
| SP303 |
Max 152 mm steel pipe. Opening is max 1.5 m2. Mortar. 3 Hr. |
SSM Mortar |
 |
|
|
| SP304 |
Max two max 457 mm wide by 127 mm deep cable trays. Opening
is max 0.37 m2. Mortar. 3 Hr. |
SSM Mortar |
 |
|
|
| SP305 |
Max 38 mm PVC pipe. Caulk only or caulk & backing options.
3 Hr. |
SSS Sealant |
 |
|
|
| SP306 |
Electrical, telephone or data cables (max 20% fill). Caulk
and backing material. 3 Hr. |
SSS Sealant |
 |
|
|
| SP307 |
Max 152 mm steel pipe or conduit. Caulk only. 3 Hr. |
SSS Sealant |
 |
|
|
| SP319 |
Max 152 mm steel pipe or conduit. Caulk and backing material.
3 Hr. |
SSS Sealant |
 |
|
|
| SP320 |
Max 76 mm copper pipe with max 13 mm glass fiber pipe insulation.
Caulk only or caulk & backing options. 3 Hr. |
SSS Sealant |
 |
|
|
| SP321 |
Electrical, telephone or data cables (max 20% fill). Putty
and backing material. 3 Hr. |
SSP Putty |
 |
|
|
| SP322 |
Max 152 mm steel pipe or conduit. Putty only. 3 Hr |
SSP Putty |
 |
|
|
| SP1053 |
Telephone or data cables (max 34% fill). PVC sleeve. Collar.
2 Hr. |
SSWRED, SSWBLU, or Factory Collar and SSP Putty |
 |
|
|
| SP1054 |
Max 203 mm diam opening. Pillows. 2 Hr. |
SSB Pillows |
 |
|
|
| SP1055 |
Max 102 mm opening. Putty. 2 Hr. |
SSP Putty |
 |
|
|
| |
| STI cUL Testing |
System No. |
Description |
STI Product |
PDF |
DWG |
DOC |
| C-AJ-0005 |
Max 102 mm diam opening. Plastic or steel sleeve option. |
LCI, SSS Sealant |
 |
 |
 |
| C-AJ-0006 |
Max 0.58 sq m opening. 2 Hr. |
Composite Sheet |
 |
 |
 |
| C-AJ-1017 |
Max 305 mm steel or iron pipe, max 102 mm copper pipe or tube,
max 51 mm flexible steel pipe, max 152 mm conduit, max102 mm
EMT or flexible Steel conduit. Caulk only or caulk & backing
options. |
LCI Sealant |
 |
 |
 |
| C-AJ-1018 |
Multiple max 305 mm steel or iron pipe or max 152 mm copper
pipe or tube, max 152 mm steel conduit, max 102 mm EMT or max
25 mm flexible steel conduit. |
Composite Sheet |
 |
 |
 |
| C-AJ-2063 |
Max 102 mm PVC, CPVC, ABS, FRPP, RNC. 3 Hr. Collar. |
SSWBLU, SSWBLU2 |
 |
 |
 |
| C-AJ-2064 |
Max 51 mm PVC, CPVC, ABS, FRPP, PVDF, RNC. 3 Hr. Tuck-in. |
SSWRED, SSWBLU, SSWBLU2 |
 |
 |
 |
| C-AJ-3010 |
Electrical, Telephone or Data Cables (45% fill). Metallic
or nonmetallic sleeve. 64 mm concrete. Caulk and backing material.
2, 3, 4 Hr. |
Putty, SSS Sealant |
 |
 |
 |
| C-AJ-3011 |
Electrical, Telephone or Data Cables (34% fill). Optional
steel sleeve. 64 mm concrete. Caulk and backing material. |
LCI Sealant |
 |
 |
 |
| C-AJ-3012 |
One or more Telephone Riser Cable. Max 82.6 mm diameter. 2
Hr. |
Composite Sheet |
 |
 |
 |
| C-AJ-4004 |
Max two aluminum or steel cable trays with electrical, telephone,
or data cables. |
SSB Pillows |
 |
 |
 |
| C-AJ-4005 |
Max 610 mm wide cable tray with electrical, telephone, or
data cables. |
Composite Sheet |
 |
 |
 |
| C-AJ-5008 |
Max 305 mm steel or iron pipe, 102 mm copper pipe/tube with
Max 51 mm thick fiberglass or mineral fiber. Optional sleeve.
64 mm concrete. |
LCI Sealant |
 |
 |
 |
| C-AJ-5009 |
Max 102 mm steel or iron, 51 mm copper pipe/tube with 13 mm
to 19 mm thick AB/PVC. Optional sleeve. Allows 64 mm concrete.
Caulk & Backing. |
LCI Sealant |
 |
 |
 |
| C-AJ-6002 |
Max 483 mm by 127 mnm Busway. |
SSB Pillows |
 |
 |
 |
| C-AJ-6003 |
Max 483 mm by 127 mm Busway. 2 Hr. |
Composite Sheet |
 |
 |
 |
| C-AJ-7003 |
Max 305 mm diam Steel Duct. Optional metallic sleeve. |
LCI Sealant |
 |
 |
 |
| C-AJ-7004 |
Max 610 mm by 305 mm Steel Duct |
LCI Sealant |
 |
 |
 |
| C-AJ-8007 |
Multiple max 102 mm steel, iron or copper with optional max
51 mm fiberglass or 19 mm or 25 mm AB/PVC or 102 mm steel conduit/EMT.
Optional thermostat wires. |
LCI Sealant |
 |
 |
 |
| C-AJ-8008 |
Multiple metal pipes or conduits with optional pipe insulation,
steel ducts, busways, or cable trays. 1.82 m x 0.91 m opening. |
SSB Pillows |
 |
 |
 |
| C-AJ-8009 |
Multiple AC Line Sets with 19 mm pipes, 13 mm AB/PVC, thermostat
wire and optional 38 mm PVC line. Optional sleeve. Caulk & Backing |
LCI, SSS Sealant |
 |
 |
 |
| C-AJ-8010 |
Multiple metal pipes or conduits, cables, cable tray, busway,
and EZ-Path. 3.4 sq m opening. |
Composite Sheet |
 |
 |
 |
| F-A-3003 |
Telephone or Data Cables (max 100% visual fill). |
EZ-Path |
 |
 |
 |
| F-A-3004 |
Telephone or Data Cables (max 100% visual fill). Kick-In Plate.
|
EZ-Path |
 |
 |
 |
| F-C-1002 |
Max 102 mm steel, iron, or copper pipe, copper tube, max 102
mm steel conduit, EMT. Optional chase wall. Caulk only. |
WF Caulk |
 |
 |
 |
| F-C-2029 |
Max 102 mm PVC, CPVC, RNC. Collar. |
SSWRED, SSWRED2, SSWBLU, SSWBLU2, LCC |
 |
 |
 |
| F-C-2031 |
Max 51 mm PVC, CPVC, RNC. Tuck-in. |
SSWBLU, SSWBLU2 |
 |
 |
 |
| F-C-2363 |
Max 2” Trade Size SCH 40 PVC pipe or conduit |
WF Caulk |
 |
 |
 |
| F-C-2364 |
One or more max ½” PEX or PEX-AL-PEX pipes or
tubes |
WF Caulk |
 |
 |
 |
| F-C-3002 |
Electrical, Telephone or Data Cables, Armored Cables or Metal
Clad Cables (45% fill). Optional chase wall. Caulk only. |
WF Caulk |
 |
 |
 |
| F-C-7001 |
Chase wall. Max 102 mm round steel duct. Caulk only. |
WF Caulk |
 |
 |
 |
| F-C-8001 |
Optional chase wall. AC Line Set with 19 mm metal pipe, 13
mm AB/PVC, 13 mm PVC line, and thermostat wire. Caulk only. |
WF Caulk |
 |
 |
 |
| W-J-3004 |
Electrical, Telephone or Data Cables (48% fill). Extended
metallic sleeve (up to 450 mm). Caulk and backing material. |
LCI, SSS Sealant, SSP Putty |
 |
 |
 |
| W-J-3005 |
Electrical, Telephone or Data Cables (max 100% visual fill).
Max seven devices. |
EZ-Path |
 |
 |
 |
| W-J-5006 |
Max 305 mm steel or iron pipe, 102 mm copper pipe/tube with
max 51 mm thick fiberglass or mineral fiber. Caulk only. |
LCI Sealant |
 |
 |
 |
| W-J-5007 |
Max 102 mm steel or iron pipe, 51 mm copper pipe/tube with
max 19 mm AB/PVC. Caulk only. |
LCI Sealant |
 |
 |
 |
| W-J-8002 |
AC Line Set with 25 mm metal pipe, 19 mm AB/PVC, and thermostat
wire. Caulk only. |
LCI Sealant |
 |
 |
 |
| W-J-8003 |
Multiple metal pipes or conduits (bare or insulated), plastic
pipe, cables, cable tray, busway, and EZ-Path. 3.4 sq m opening. |
Composite Sheet |
 |
 |
 |
| W-L-1015 |
Rectangular opening. Multiple 102 mm steel or iron pipes,
conduits or EMT. Studs bypass opening. Caulk only. |
LCI, SSS Sealant |
 |
 |
 |
| W-L-1016 |
Max203 mm steel or iron pipe, 102 mm copper pipe/tube, 32
mm flexible pipe, 152 mm conduit, 102 mm EMT, or 25 mm flexible
conduit. Caulk only. |
LCI Sealant |
 |
 |
 |
| W-L-2049 |
Max 102 mm PVC, CPVC, RNC. Collar. |
SSWRED, SSWRED2, SSWBLU, SSWBLU2, LCC |
 |
 |
 |
| W-L-2053 |
Max 51 mm PVC, CPVC, RNC. Tuck-in. |
SSWBLU, SSWBLU2 |
 |
 |
 |
| W-L-3008 |
Electrical, Telephone or Data Cables, Armored Cables or Metal
Clad Cables (114 mm bundle). Caulk only. |
LCI Sealant |
 |
 |
 |
| W-L-3009 |
Electrical, Telephone or Data Cables, Armored Cables or Metal
Clad Cables (48% fill). Extended metallic sleeve. Caulk and
backing material. |
LCI, SSS Sealat, SSP Putty |
 |
 |
 |
| W-L-3010 |
Electrical, Telephone or Data Cables, max 38 mm OFR (max 100%
visual fill). Max seven devices. |
EZ-Path |
 |
 |
 |
| W-L-3011 |
Electrical, Telephone or Data Cables, max 38 mm OFR (max 100%
visual fill). EZ Path (max seven devices). EZ Path Mini. |
Composite Sheet |
 |
 |
 |
| W-L-4002 |
Open ladder aluminum or steel cable tray with electrical,
telephone, or data cables. |
SSB Pillows |
 |
 |
 |
| W-L-5017 |
Max 152 mm steel or iron pipe, 102 mm copper pipe/tube with
max 51 mm thick fiberglass or mineral fiber. Caulk only. |
LCI Sealant |
 |
 |
 |
| W-L-5018 |
Max 102 mm steel or iron pipe, 51 mm copper pipe/tube with
max 19 mm AB/PVC. Caulk only. |
LCI Sealant |
 |
 |
 |
| W-L-6001 |
Max 483 mm by 127 mm Busway |
SSB Pillows |
 |
 |
 |
| W-L-7004 |
Max 610 x 762 mm steel duct. Caulk only. Steel retaining angles. |
LCI Sealant |
 |
 |
 |
| W-L-7005 |
Max 203 mm round steel duct. Caulk only. |
LCI Sealant |
 |
 |
 |
| W-L-7006 |
Max 203 mm x 203 mm steel duct. Caulk only. No retaining angles. |
LCI Sealant |
 |
 |
 |
| W-L-8003 |
AC Line Set with 25 mm metal pipe, 19 mm AB/PVC, and thermostat
wire. Caulk only. |
LCI Sealant |
 |
 |
 |
| W-L-8004 |
Multiple bare or insulated (51 mm fiberglass, MW, or 19 mm
AB/PVC) metal pipes, PVC/CPVC/RNC/ENT, 51 mm cable bundle. Caulk
& Backing. |
LCI Sealant |
 |
 |
 |
| W-L-8005 |
Multiple metal pipes or conduits. Optional 51 mm fiberglass,
19 mm AB/PVC, or 75 mm cellular glass. 0.48 sq m opening. |
SSB Pillows |
 |
 |
 |
| W-L-8006 |
Multiple metal pipes, conduits, or plastic pipes (DWV or closed),
optional fiberglass insulation on metal pipes, or cables. |
Composite Sheet |
 |
 |
 |
| W-L-8007 |
Multiple metal pipes or conduits (bare or insulated), plastic
pipe, cables, cable tray, busway, and EZ-Path. 3.4 sq m opening. |
Composite Sheet |
 |
 |
 |