STI Firestop Specifications Distributors





 


Maple Leaf All STI firestopping systems tested at Underwriters Laboratories Inc. (UL) are also concurrently classified for use in Canada. Such Listings appear in UL's “Products Certified for Canada” directory. STI also conducts tests at UL's sister company, Underwriters Laboratories of Canada (ULC).

The primary difference between Canadian test requirements and those found in the US relates to vented combustible penetrants such as plastic pipes intended for use in drain, waste, or vent (DWV) applications. Said penetrating items must be tested with a minimum positive furnace pressure differential of 50 Pa compared to 2.5 Pa for the US. Other than vented combustible penetrants, all other penetrating items are tested to 2.5 Pa.

The following links provide additional information on products and systems certified for use in Canada:

Canadian General Firestopping (07 84 00)

Letter From UL/ULC RE: Relationship Between UL & ULC

General Certificate of Conformance specific for Canada

Fill, Void Or Cavity Materials Certified for Canada

Guide Info for Through-penetration Firestop Systems Certified for Canada

Guide Info for Joint Systems Certified for Canada


STI 50 Pa Testing for Combustible Pipes
System No.
Pipe Diameter (mm)
STI Product
PDF DWG DOC
SPC87 Max 150 mm FRPP pipe. Collar. 2 Hr. SSWRED, SSWBLU, or Factory Collar PDF    
SPC88 Max 100 mm ABS or FRPP pipe. Collar. 2 Hr. SSWRED, SSWBLU, or Factory Collar PDF    
SPC89 Max 50 mm ABS or FRPP pipe. Tuck-in. 2 Hr. SSWBLU PDF    
SPC90 Max 100 mm PVDF pipe. Collar. 2 Hr. SSWRED, SSWBLU, or Factory Collar PDF    
 
STI ULC Testing (Supplemental to UL/cUL Listings)
System No.
Description
STI Product
PDF DWG DOC
SP303 Max 152 mm steel pipe. Opening is max 1.5 m2. Mortar. 3 Hr. SSM Mortar PDF    
SP304 Max two max 457 mm wide by 127 mm deep cable trays. Opening is max 0.37 m2. Mortar. 3 Hr. SSM Mortar PDF    
SP305 Max 38 mm PVC pipe. Caulk only or caulk & backing options. 3 Hr. SSS Sealant PDF    
SP306 Electrical, telephone or data cables (max 20% fill). Caulk and backing material. 3 Hr. SSS Sealant PDF    
SP307 Max 152 mm steel pipe or conduit. Caulk only. 3 Hr. SSS Sealant PDF    
SP319 Max 152 mm steel pipe or conduit. Caulk and backing material. 3 Hr. SSS Sealant PDF    
SP320 Max 76 mm copper pipe with max 13 mm glass fiber pipe insulation. Caulk only or caulk & backing options. 3 Hr. SSS Sealant PDF    
SP321 Electrical, telephone or data cables (max 20% fill). Putty and backing material. 3 Hr. SSP Putty PDF    
SP322 Max 152 mm steel pipe or conduit. Putty only. 3 Hr SSP Putty PDF    
SP1053 Telephone or data cables (max 34% fill). PVC sleeve. Collar. 2 Hr. SSWRED, SSWBLU, or Factory Collar and SSP Putty PDF    
SP1054 Max 203 mm diam opening. Pillows. 2 Hr. SSB Pillows PDF    
SP1055 Max 102 mm opening. Putty. 2 Hr. SSP Putty PDF    
 
STI cUL Testing
System No.
Description
STI Product
PDF DWG DOC
C-AJ-0005 Max 102 mm diam opening. Plastic or steel sleeve option. LCI, SSS Sealant pdf dwg doc
C-AJ-0006 Max 0.58 sq m opening. 2 Hr. Composite Sheet pdf dwg doc
C-AJ-1017 Max 305 mm steel or iron pipe, max 102 mm copper pipe or tube, max 51 mm flexible steel pipe, max 152 mm conduit, max102 mm EMT or flexible Steel conduit. Caulk only or caulk & backing options. LCI Sealant pdf dwg doc
C-AJ-1018 Multiple max 305 mm steel or iron pipe or max 152 mm copper pipe or tube, max 152 mm steel conduit, max 102 mm EMT or max 25 mm flexible steel conduit. Composite Sheet pdf dwg doc
C-AJ-2063 Max 102 mm PVC, CPVC, ABS, FRPP, RNC. 3 Hr. Collar. SSWBLU, SSWBLU2 pdf dwg doc
C-AJ-2064 Max 51 mm PVC, CPVC, ABS, FRPP, PVDF, RNC. 3 Hr. Tuck-in. SSWRED, SSWBLU, SSWBLU2 pdf dwg doc
C-AJ-3010 Electrical, Telephone or Data Cables (45% fill). Metallic or nonmetallic sleeve. 64 mm concrete. Caulk and backing material. 2, 3, 4 Hr. Putty, SSS Sealant pdf dwg doc
C-AJ-3011 Electrical, Telephone or Data Cables (34% fill). Optional steel sleeve. 64 mm concrete. Caulk and backing material. LCI Sealant pdf dwg doc
C-AJ-3012 One or more Telephone Riser Cable. Max 82.6 mm diameter. 2 Hr. Composite Sheet pdf dwg doc
C-AJ-4004 Max two aluminum or steel cable trays with electrical, telephone, or data cables. SSB Pillows pdf dwg doc
C-AJ-4005 Max 610 mm wide cable tray with electrical, telephone, or data cables. Composite Sheet pdf dwg doc
C-AJ-5008 Max 305 mm steel or iron pipe, 102 mm copper pipe/tube with Max 51 mm thick fiberglass or mineral fiber. Optional sleeve. 64 mm concrete. LCI Sealant pdf dwg doc
C-AJ-5009 Max 102 mm steel or iron, 51 mm copper pipe/tube with 13 mm to 19 mm thick AB/PVC. Optional sleeve. Allows 64 mm concrete. Caulk & Backing. LCI Sealant pdf dwg doc
C-AJ-6002 Max 483 mm by 127 mnm Busway. SSB Pillows pdf dwg doc
C-AJ-6003 Max 483 mm by 127 mm Busway. 2 Hr. Composite Sheet pdf dwg doc
C-AJ-7003 Max 305 mm diam Steel Duct. Optional metallic sleeve. LCI Sealant pdf dwg doc
C-AJ-7004 Max 610 mm by 305 mm Steel Duct LCI Sealant pdf dwg doc
C-AJ-8007 Multiple max 102 mm steel, iron or copper with optional max 51 mm fiberglass or 19 mm or 25 mm AB/PVC or 102 mm steel conduit/EMT. Optional thermostat wires. LCI Sealant pdf dwg doc
C-AJ-8008 Multiple metal pipes or conduits with optional pipe insulation, steel ducts, busways, or cable trays. 1.82 m x 0.91 m opening. SSB Pillows pdf dwg doc
C-AJ-8009 Multiple AC Line Sets with 19 mm pipes, 13 mm AB/PVC, thermostat wire and optional 38 mm PVC line. Optional sleeve. Caulk & Backing LCI, SSS Sealant pdf dwg doc
C-AJ-8010 Multiple metal pipes or conduits, cables, cable tray, busway, and EZ-Path. 3.4 sq m opening. Composite Sheet pdf dwg doc
F-A-3003 Telephone or Data Cables (max 100% visual fill). EZ-Path pdf dwg doc
F-A-3004 Telephone or Data Cables (max 100% visual fill). Kick-In Plate. EZ-Path pdf dwg doc
F-C-1002 Max 102 mm steel, iron, or copper pipe, copper tube, max 102 mm steel conduit, EMT. Optional chase wall. Caulk only. WF Caulk pdf dwg doc
F-C-2029 Max 102 mm PVC, CPVC, RNC. Collar. SSWRED, SSWRED2, SSWBLU, SSWBLU2, LCC pdf dwg doc
F-C-2031 Max 51 mm PVC, CPVC, RNC. Tuck-in. SSWBLU, SSWBLU2 pdf dwg doc
F-C-2363 Max 2” Trade Size SCH 40 PVC pipe or conduit WF Caulk pdf dwg doc
F-C-2364 One or more max ½” PEX or PEX-AL-PEX pipes or tubes WF Caulk pdf dwg doc
F-C-3002 Electrical, Telephone or Data Cables, Armored Cables or Metal Clad Cables (45% fill). Optional chase wall. Caulk only. WF Caulk pdf dwg doc
F-C-7001 Chase wall. Max 102 mm round steel duct. Caulk only. WF Caulk pdf dwg doc
F-C-8001 Optional chase wall. AC Line Set with 19 mm metal pipe, 13 mm AB/PVC, 13 mm PVC line, and thermostat wire. Caulk only. WF Caulk pdf dwg doc
W-J-3004 Electrical, Telephone or Data Cables (48% fill). Extended metallic sleeve (up to 450 mm). Caulk and backing material. LCI, SSS Sealant, SSP Putty pdf dwg doc
W-J-3005 Electrical, Telephone or Data Cables (max 100% visual fill). Max seven devices. EZ-Path pdf dwg doc
W-J-5006 Max 305 mm steel or iron pipe, 102 mm copper pipe/tube with max 51 mm thick fiberglass or mineral fiber. Caulk only. LCI Sealant pdf dwg doc
W-J-5007 Max 102 mm steel or iron pipe, 51 mm copper pipe/tube with max 19 mm AB/PVC. Caulk only. LCI Sealant pdf dwg doc
W-J-8002 AC Line Set with 25 mm metal pipe, 19 mm AB/PVC, and thermostat wire. Caulk only. LCI Sealant pdf dwg doc
W-J-8003 Multiple metal pipes or conduits (bare or insulated), plastic pipe, cables, cable tray, busway, and EZ-Path. 3.4 sq m opening. Composite Sheet pdf dwg doc
W-L-1015 Rectangular opening. Multiple 102 mm steel or iron pipes, conduits or EMT. Studs bypass opening. Caulk only. LCI, SSS Sealant pdf dwg doc
W-L-1016 Max203 mm steel or iron pipe, 102 mm copper pipe/tube, 32 mm flexible pipe, 152 mm conduit, 102 mm EMT, or 25 mm flexible conduit. Caulk only. LCI Sealant pdf dwg doc
W-L-2049 Max 102 mm PVC, CPVC, RNC. Collar. SSWRED, SSWRED2, SSWBLU, SSWBLU2, LCC pdf dwg doc
W-L-2053 Max 51 mm PVC, CPVC, RNC. Tuck-in. SSWBLU, SSWBLU2 pdf dwg doc
W-L-3008 Electrical, Telephone or Data Cables, Armored Cables or Metal Clad Cables (114 mm bundle). Caulk only. LCI Sealant pdf dwg doc
W-L-3009 Electrical, Telephone or Data Cables, Armored Cables or Metal Clad Cables (48% fill). Extended metallic sleeve. Caulk and backing material. LCI, SSS Sealat, SSP Putty pdf dwg doc
W-L-3010 Electrical, Telephone or Data Cables, max 38 mm OFR (max 100% visual fill). Max seven devices. EZ-Path pdf dwg doc
W-L-3011 Electrical, Telephone or Data Cables, max 38 mm OFR (max 100% visual fill). EZ Path (max seven devices). EZ Path Mini. Composite Sheet pdf dwg doc
W-L-4002 Open ladder aluminum or steel cable tray with electrical, telephone, or data cables. SSB Pillows pdf dwg doc
W-L-5017 Max 152 mm steel or iron pipe, 102 mm copper pipe/tube with max 51 mm thick fiberglass or mineral fiber. Caulk only. LCI Sealant pdf dwg doc
W-L-5018 Max 102 mm steel or iron pipe, 51 mm copper pipe/tube with max 19 mm AB/PVC. Caulk only. LCI Sealant pdf dwg doc
W-L-6001 Max 483 mm by 127 mm Busway SSB Pillows pdf dwg doc
W-L-7004 Max 610 x 762 mm steel duct. Caulk only. Steel retaining angles. LCI Sealant pdf dwg doc
W-L-7005 Max 203 mm round steel duct. Caulk only. LCI Sealant pdf dwg doc
W-L-7006 Max 203 mm x 203 mm steel duct. Caulk only. No retaining angles. LCI Sealant pdf dwg doc
W-L-8003 AC Line Set with 25 mm metal pipe, 19 mm AB/PVC, and thermostat wire. Caulk only. LCI Sealant pdf dwg doc
W-L-8004 Multiple bare or insulated (51 mm fiberglass, MW, or 19 mm AB/PVC) metal pipes, PVC/CPVC/RNC/ENT, 51 mm cable bundle. Caulk & Backing. LCI Sealant pdf dwg doc
W-L-8005 Multiple metal pipes or conduits. Optional 51 mm fiberglass, 19 mm AB/PVC, or 75 mm cellular glass. 0.48 sq m opening. SSB Pillows pdf dwg doc
W-L-8006 Multiple metal pipes, conduits, or plastic pipes (DWV or closed), optional fiberglass insulation on metal pipes, or cables. Composite Sheet pdf dwg doc
W-L-8007 Multiple metal pipes or conduits (bare or insulated), plastic pipe, cables, cable tray, busway, and EZ-Path. 3.4 sq m opening. Composite Sheet pdf dwg doc

www.ul.com
www.ulc.ca

    Back
     