                   EZ-Path Home

EZ-Estimator

How many EZ-Paths do you need?

STI Project List

Select your cable size from the left-hand columns to determine maximum capacity of pathways.

Cable Diameter
Pathway Cable Capacity
mm
inches
EZD22
Series
EZD33
Series
EZD44
Series
3 0.118 78 395 822
3.5 0.138 57 290 604
4 0.157 44 222 462
4.5 0.177 34 175 365
5 0.197 28 142 296
5.5 0.216 23 117 244
6 0.236 19 98 205
6.5 0.256 16 84 175
7 0.275 14 72 151
8 0.314 11 55 115
9 0.354 8 43 91
12.5 0.491 4 22 47
15 0.590 3 15 32
18 0.708 2 10 22
20 0.786 1 8 18
25 0.983 1 5 11
30 1.179 0 3 8
35 1.376 0 2 6

Use this quick and easy calculator to figure out the size and number of EZ-Path sleeves required for each barrier penetration.

NOTE: This calculator assumes use of cable installation practices that maximize pathway utilization. The calculated results should be considered the minimum required. Download Maximize EZ-Path Capacity to identify additional factors that may influence the number of pathways required for your installation.

1. Select your cable size by clicking the cable diameter in the table at left.
2. Enter the number of cables you will be installing now.
3. Enter a value for cables you may be adding in the future.


Cable Diameter: Choose from column at left
 
Cables to be installed:

CABLES NOW

CABLES FUTURE
 
Pathways Required:

TOTAL CABLES

EZD22

EZD33

 

EZD44


Pathway Capacity Chart
(Pathway Cable Capacity Chart)

 


IMPORTANT NOTICE: The information herein is theoretical and is provided for informational purposes only. Variations in cable size and shape, as well as cable bundle size and other factors may influence these calculations. Therefore, THE ACCURACY OF THIS INFORMATION CANNOT BE GUARANTEED.
  U.S. Patent 6,732,481 Back
     